Title |
Anti-islanding Detection of Photovoltaic Inverter Based on Negative Sequence Voltage Injection to Grid |
Authors |
Byeong-Heon Kim ; Yong-Soon Park ; Seung-Ki Sul ; Woo-Chull Kim ; Hyun-Young Lee |
DOI |
10.6113/TKPE/2012.17.6.546 |
Keywords |
anti-islanding detection; negative sequence voltage injection; negative sequence equivalent circuit; photovoltaic systems |
Abstract |
This paper presents an active anti-islanding detection method using negative sequence voltage injection to the grid through a three-phase photovoltaic inverters. Because islanding operation mode can cause a variety of problems, the islanding detection of grid-connected photovoltaic inverter is the mandatory feature. The islanding mode is detected by measuring the magnitude of negative sequence impedance calculated by the negative sequence voltage and current at the point of common coupling. Simulation and experimental test are performed to verify the effectiveness of the proposed method which can detect the islanding mode in the specified time. The test has been done in accordance with the condition on IEEE Std 929-2000. |