Title |
Realtime Compensation of PCC Voltage Variation by Injection of Required Reactive Power in a Grid Connected Variable Speed Wind Turbine |
Authors |
Ji-Hoon Im ; Seung-Ho Song |
DOI |
10.6113/TKPE/2010.15.1.69 |
Keywords |
Voltage Variation; PCC Voltage; Reactive Power Compensation |
Abstract |
In a grid connected variable speed wind turbine, the PCC voltage and the wind power fluctuate as the wind velocity changed. And this voltage variation is changed due to location of PCC. This paper calculate the value of PCC voltage variation which is proportional to the product of the line impedance from the ideal generator to the PCC and the wind turbine output current. And to reduce this PCC voltage variation, this paper calculate the required reactive power analytically using the vector diagram method. Output reactive current is changed, if the reactive current is limited by inverter capacity or grid code have the margin of voltage variation. If the grid connected inverter is controlled by proposed algorithm, the PCC voltage variation is minimized though the wind turbine output change at random. To verify calculated voltage variation and required reactive power, this paper utilized Matlab and PSCAD/EMTDC simulation and real small wind turbine and power system in Sapsido, island in the Yellow Sea. |